|
Designs
for Comfortable Heating & Cooling Systems
Air Comfort
Designs provides Homeowners, Do it Yourselfers, Contractors and
Distributors a heating and air conditioning, ACCA Manual J design
with a scaled floor plan detailing duct and piping layouts and a
materials and equipment list.
V
Scroll down for Glossary V
The
ACCA Connection
Right-J8 and Right-JD are recognized by ACCA as their official software
versions of the Manual J and Manual D calculation and sizing methods.
What
is ACCA?
The Air Conditioning Contractors of America (ACCA) is a nonprofit
trade association of HVACR contractors with national headquarters
located in Washington D.C. With over 3,400 members and more than
50 local chapters across the country, ACCA’s membership includes
manufacturers of HVAC equipment, utilities, equipment wholesalers
and distributors, vocational and technical schools and others.
ACCA represents and serves contractors who design, install, service
and repair air conditioning, heating, refrigeration, humidification,
dehumidification, air purification and ventilation systems. ACCA
is dedicated to providing its members with the tools and information
for managing quality in their business operations through numerous
education programs, publications, and technical and management reference
libraries.
In addition, ACCA vigorously promoted the interests and concerns
of its members to the US Congress and federal agencies and encourages
input and participation from members in the association’s
goal to influence public policy to improve the HAVC business climate.
Air
change – The amount of outdoor air required
to completely replace the air in a room or building with outdoor
air, by air leakage (infiltration) and/or through an engineered
ventilation system.
Air
changes per hour – The number of times per
hour the total volume of indoor air contained in a room or building
is replaced with outdoor air by infiltration or mechanical ventilation.
Air
conditioner – An assembly of equipment for
the simultaneous control of air temperature, relative humidity,
purity and motion.
Air
Conditioning System – a system that consists
of air exchangers, blowers, filters, supply and return-air systems,
and shall include any apparatus installed in connection therewith.
Air
Conditioning Contractors of America (ACCA) – A
nonprofit trade association of HVACR contractors. (See the end of
this Glossary)
Airflow
– The movement of air, usually within boundaries
such as ducts.
Air
outlet – A device or opening through which
air is withdrawn from or discharged into a conditions space.
Air
Volumetric Flow (AVF) – Refers to the air
flow rate through an HVAC unit or duct system. Measured in cubic
feet per minute (cfm).
Annual
fuel consumption – The amount of fuel used
in one year.
Annual
fuel utilization efficiency (AFUE) – An annual
fuel efficiency rating similar to mileage ratings for cars. The
higher the ARUE for a furnace, the more efficient the furnace. All
furnace models are tested using U.S. Department of Energy procedures
to assign their AFUE rating.
Ambient
Air – The air surrounding an object (usually
outdoor air or the air in an enclosure under study). American Society
of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
An international organization that is organized for the sole purpose
of advancing the arts and sciences of heating, ventilation, air
conditioning and refrigeration for the public’s benefit through
research, standards writing, continuing education and publications.
Boiler (Residential) – A self contained appliance from which
water is heated by any number of fuels. The heated water is circulated
for heating purposes and then returned to the boiler, and which
operates at water pressure not exceeding 30 pounds per square inch
and water temperatures not exceeding 250.
Boiler:
A container or vessel in which a liquid is heated
using any heat source.
Building
Thermal Envelope – The basement walls, exterior
walls, floor, roof, and any other building element that enclose
conditioned spaces.
Ceiling
Height - level and flat – measurement from
floor to ceiling. cathedral – measurement from floor to lowest
point and floor to highest point.
Chimney
– A primarily vertical structure containing
one or more flues, for the purpose of carrying gaseous products
of combustion and air from a fuel-burning appliance to the outside
atmosphere.
Chimney
Connector - A pipe that connects a fuel-burning
appliance to a chimney. Also called a vent.
Chimney
Types - Residential-type appliance. An approved
chimney for removing the products of combustion from fuel-burning,
residential-type appliances producing combustion gases not in excess
of 1,000_F under normal operating conditions, but capable of producing
combustion gases of 1,400_F during intermittent forced firing for
periods up to 1 hour. All temperatures shall be measured at the
appliance flue outlet. Residential-type appliance chimneys include
masonry and factory-built types.
Cooling
– The process for reducing the temperature
of a space of system below a specified level.
Cooling
load temperature difference – Used to calculate
the heat gain for walls, ceilings, floors and opaque doors. A CLTD
represents the effective air temperature difference across the structural
panel. This temperature difference accounts for the air-to-air temperature
difference across the panel, the heating effect of the sun striking
the outdoor surface of the panel and the thermal mass of the panel.
Cooling
in side dry-bulb – The temperature used to
set the thermostat during the cooling season.
Cold
Wall – any wall that faces an unconditioned
area but is not an outside wall. Example: an unconditioned garage.
Combustion
Air – The air provided to fuel-burning equipment
including air for fuel combustion, draft hood dilution and ventilation
of the equipment enclosure.
Condensate
– The liquid that separates from a gas due
to a reduction in temperature, e.g., water that condenses from flue
gases and water that condenses from air circulating through the
cooling coil in air conditioning equipment.
Condensing
Appliance – An appliance that condenses water
generated by the burning of fuels.
Conditioned
Area – That area within a building provided
with heating and/or cooling systems or appliances capable of maintaining,
through design or heat loss/gain, a comfortable environment during
the heating/cooling season and/or has a fixed opening directly adjacent
to a conditioned area.
Conditioned
Area – an area which is either heated or cooled
by mechanical means.
Conditioned
Floor Area – The horizontal projection of
the floor associated with the conditioned space.
Condition
Floor Space – For energy purposes, space within
a building that is provided with heating and/or cooling equipment
or systems capable of maintaining, through design or heat loss/gain,
50_F during the heating season and 85_ during the cooling season,
or communicates directly with a conditioned space. For mechanical
purposes, an area, room or space being heated or cooled by any equipment
or appliance.
Construction
Documents Design – Written, graphic and pictorial
documents prepared or assembled for describing the design, location
and physical characteristics of the elements of a project necessary
for obtaining a building permit or calculating a heat loss/gain.
Construction drawings shall be drawn to an appropriate scale.
Control,
Limit – An automatic control responsive to
changes in liquid flow or level, pressure, or temperature for limiting
the operation of an appliance.
Control,
Primary Safety – A safety control responsive
directly to flame properties that senses the presence or absence
of flame and, in event of ignition failure or unintentional flame
extinguishments, automatically causes shutdown of mechanical equipment.
Convector
– A system incorporating heating elements
in an enclosure in which air enters an opening below the heating
element, is heated and leaves the enclosure through an opening located
above the heating element. Example: copper fin-tube baseboard heat
Cubic
feet per minute (cfm) – The volume of air
that can be heated or cooled by heating or cooling equipment per
minute.
Damper,
Volume – A device that will restrict, retard
or direct the flow of air in any duct, or the products of combustion
of heat-producing equipment, vent connector, vent or chimney.
Design,
as provided by “"air comfort
designs"” (also known in the technical field
as a heat loss/gain)– A document assembled for the purpose
of determining the correct size of heating and/or air conditioning
equipment and/or the correct amount of distribution piping or ductwork
to condition a structure. The “design” is calculated
using Right-J8 and Right-D which is recognized by ACCA (The Air
Conditioning Contractors of America) as their official software
versions of the Manual J and Manual D calculation and sizing methods.
The “design” would list each room of the structure showing
the amount of BTU’s and related output means to properly condition
a room and collectively the structure. The necessary information
such as window and door sizes, room sizes, ceiling heights, outside
wall dimensions, insulation effectiveness and quantities, climate,
direction that walls face, interior design temperature, type of
heat and type of fuel are used to attain this calculation. The “design”
is primarily used as a sizing tool for any new, additional, supplemental
or replacement heating or air conditioning project. A “design”
is also required in many municipalities of the country to acquire
a permit before proceeding with a new project.
Design/Layout
– A “design” with the addition
of a scaled floor plan showing the complete single or multiple story
structure with the heating/air conditioning equipment. All main
supply and return ductwork and branches are shown sized to scale
and color coded. A complete material list is supplied with an option
for pricing. A “design/layout” is compiled as a presentation
ready for a customer or installer to review (Contractor, HVAC Distributor),
ready for a contractor to estimate from (Homeowner) or ready for
a trip to the supply house (DIY).
Design
airflow – The required airflow when the system
is operating under assumed maximum conditions of design.
Design
conditions – The specified environmental conditions,
such as temperature and humidity, required to be produced and maintained
by a system.
Design
Professional – An individual who is registered,
licensed or certified to practice their respective design profession
as defined by the requirements of the registration laws of the state,
city, or jurisdiction.
Design
swing – The temperature rise allowed above
the inside design temperature.
Direct-Vent
Appliance – A fuel-burning appliance with
a sealed combustion system that draws all air for combustion from
the outside atmosphere and discharges all flue gases to the outside
atmosphere.
Draft
– The pressure difference existing between
the appliance or any component part and the atmosphere that causes
a continuous flow of air and products of combustion through the
gas passages of the appliance to the atmosphere.
Induced
draft – The pressure difference created by
the action of a fan, blower or ejector that is located between the
appliance and the chimney or vent termination.
Natural
draft – The pressure difference created by
a vent or chimney because of its height, and the temperature difference
between the flue gases and the atmosphere.
Dry-bulb
temperature – Air temperature measured by
an ordinary thermometer when there is no solar heating effect or
evaporative cooling effect.
Duct
sizing – The calculation of dimensions of
ducting for a given air distribution system
Duct
System - A continuous passageway for the transmission
of air, which, in addition to ducts, includes duct fittings, dampers,
plenums, fans and accessory air-handling equipment and appliances.
Efficiency
– The ratio of useful output energy of a piece
of equipment to input energy.
Energy-efficiency
ratio (EER) – The ratio of net cooling capacity
in Btuh to the total rate of electric input in watts, under designated
operating conditions.
Equipment
– All piping, ducts, vents, control devices
and other components of systems other than appliances that are permanently
installed and integrated to provide control of the environmental
conditions for buildings.
Equipment
sizing load – Also called design heating or
cooling load.
Equivalent
length – A method of expressing the friction
loss of duct firings by equating the firing loss to straight duct
friction loss.
Exterior
Wall – An above-grade wall enclosing conditioned
space. Includes between floor joists, peripheral edges of floors,
roof and basement knee walls, dormer walls, gable end walls, walls
enclosing a mansard roof, and basement walls with an average below
grade wall area that is less than 50 percent of the total opaque
and non opaque area of the enclosing side.
Fahrenheit
temperature (_F) – The temperature scale on
which at standard atmospheric pressure, the boiling point of water
is 212 _F and its freezing point is 32_F: absolute zero is –459.69_F.
Fenestration
- Skylights, roof windows, vertical windows (whether
fixed or moveable); opaque doors; glazed doors; glass block; and
combination opaque/glazed doors.
Fireplace
– An assembly consisting of hearth and fire
chamber of noncombustible material and provided with a chimney,
for use with solid fuels.
Factory-built
fireplace – A listed and labeled fireplace
and chimney system composed of factory-made components, and assembled
in the field in accordance with manufacturer’s instructions
and the conditions of the listing.
Forced
air: a
distribution system in which a fan circulates air from a heating
or cooling unit to rooms through a network of ducts.
Forced-draft
venting system – A
portion of a venting system using a fan or other mechanical means
to cause the removal of flue or vent gases under positive static
pressure.
Fireplace
Stove – A freestanding, chimney-connected
solid-fuel burning heater designed to be operated with the fire
chamber doors in either open or closed position.
Floor
Furnace – A self-contained furnace suspended
from the floor of the space being heated, taking air for combustion
from outside such space, and with means for lighting the appliance
from such space.
Floor
plan: The drawing of a structure with the view from
overhead looking down. The drawing would include exterior and interior
walls, windows, doors, skylights, and staircases. “air comfort
designs” floor plan also shows colored lines depicting a furnace,
ductwork, registers and related equipment or a boiler and related
piping and heat.
Flue
Gases – Products of combustion plus excess
air in appliance flues or heat exchangers.
Friction
rate – The pressure loss that occurs between
two points in duct system.
Fuel-Piping
System – All piping, tubing, valves and fittings
used to connect fuel utilization equipment to the point of fuel
delivery.
Furnace
– A vented heating appliance designed or arranged
to discharge heated air into a conditioned space or through a duct
or ducts.
Gas
Appliance Manufactures Association – A national
trade association whose members manufacture appliances, components
and related products used in connection with space heating water,
water heating and commercial food service. In addition to gas-fired
appliances, GAMA’s scope includes certain oil-fired and electrical
appliances. GAMA’s principal purpose is to serve and represent
its members and the industries, which they comprise
Ground-Source
Heat Pump Loop System – Piping buried in horizontal
or vertical excavations or placed in a body of water for the purpose
of transporting heat transfer liquid to and from a heat pump. Included
in this definition are closed loop systems in which the liquid is
re circulated through open loop systems in which the liquid is drawn
from a well or other source.
Habitable
Space – A space in a building for living,
sleeping, eating or cooking. Bathrooms, toilet rooms, closets, halls,
storage or utility spaces and similar areas are not considered habitable
spaces.
Heat
gain: the amount of heat gained and measured in
BTU’s from a space to be conditioned, at the summer outdoor
design temperature and a specified indoor design condition.
Heat
flow – The passage of heat from one point
to another or one space to another by one or more of the three mode
(conduction, convection and radiation).
Heat
loss: the amount of heat lost and measured in BTU’s
from a space to be conditioned, at the winter outdoor design temperature
and a specified indoor design condition.
Heat
Pump – An appliance having heating or heating/cooling
capability and that uses refrigerants to extract heat from air,
liquid or other sources.
Heat transfer multiplier (HTM) – The amount of heat that flows
through one square foot of a building component at a given temperature
difference. HTM values differ for various wall constructions. Heating
HTM’s for doors, walls, etc. are determined by multiplying
the transmission coefficient (U) by the winter design temperature
difference. Cooling HTM’s for doors, walls, etc. are determined
by multiplying the transmission coefficient (U) by the summer equivalent
temperature difference.
Heating
– The process of adding heat energy causing
a raise in temperature, or a transfer of sensible heat into latent
heat.
Heating
inside dry-bulb – The temperature used to
set the thermostat during the heating season.
Heating
load – The heating rate required to replace
heat loss from the space being controlled.
Heating
seasonal performance factor – The ratio of
the total heat delivered over the heating seasons (not to exceed
12 months) to the total energy input over the heating season, in
consistent units.
Heating, Ventilation and Air Conditioning (HVAC)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Hour
– One of the points on a timepiece marking
off 12 or 24 successive intervals of 60 minutes, from midnight to
noon and noon to midnight to midnight.
Humidity
ratio – The ratio of the mass of water vapor
to the mass of dry air.
Hydronic
– Commonly called hot water or steam heat.
Hot water heating uses a boiler to heat water with any fuel. The
heated water is then circulated throughout a distribution piping
system using either gravity or a circulator and released into the
conditioned area though radiation or convection. Hot water is common
in residential and commercial buildings. Steam heat uses a boiler
to heat water with any fuel. The water is heated to produce steam
in the boiler and pressure pushes the steam from the boiler through
distribution piping to the final release point. Steam heat is commonly
used in commercial and industrial applications.
Kilowatt
hour (kWh) – The energy unit used in marketing
electrical power (the SI unit for energy is the joule (J))
Latent
gain – The additional load caused by humidity
reduction. Affected by the relative humidity.
Latent
heat – Energy (heat) associated with a change
of state, as of liquid to vapor or vice versa, expressed a Btu/lb.
In HVAC usage, the energy associated with the moisture in the air.
Latent
infiltration Load – The heat gain or latent
load from moisture brought in with the air leakage.
Latent
ventilation Load – The latent gain caused
by mechanical ventilation equipment.
Length
– A measure used as a unit to estimate dimensions.
Linear
foot – A unit of length in the U.S. Customary
and British Imperial systems equal to 12 inches (0.3048 meter).
Listed
And Listing – Terms referring to equipment
that is shown in a list published by an approved testing agency
qualified and equipped for experimental testing and maintaining
and adequate periodic inspection of current productions and whose
listing states that the equipment complies with nationally recognized
standards when installed in accordance with the manufacturer’s
installation instructions.
Living
Space – Space within a dwelling unit utilized
for living, sleeping, eating, cooking, bathing, washing, and sanitation
purposes.
Load
calculation – Determines how much energy (Btu)
is required to maintain cooling, heating, and ventilation.
Masonry
chimney – A field-constructed chimney comprised
of solid masonry units, bricks, stones or concrete.
Masonry
fireplace – A field-constructed fireplace
composed solid masonry units, bricks, stones or concrete.
Manual
D – ACCA’s method for sizing residential
ductwork. Right-Suite Residential is the computerized version of
Manual D.
Manual
J – ACCA’s method for sizing residential
load calculations. Right-Suite Residential is the computerized version
of Manual J.
Mechanical
System – A system specifically addressed and
regulated by code and composed of components, devices, appliances
and equipment.
Mechanical
Draft System – A venting system designed to
remove flue or vent gases by mechanical means to cause the removal
of flue or spent gases under non positive static vent pressure.
Multi
zone (or multiple zone) system –
For dwellings, a comfort-conditioning system designed to serve two
or more rooms or areas having different or unsynchronized heating
and cooling requirements. In some cases a zone is required to satisfy
a special humidification, filtration or ventilation requirement.
Natural
Draft System – A venting system designed to
remove flue or vent gases under non positive static vent pressure
entirely by natural draft.
Non
conditioned Space – A
Space that does not have insulated walls, floors or ceilings and
has no means for heating or cooling.
Outdoor
air – The air outside a building or taken
from outdoors and not previously circulated through the system.
Outside
air – External air; atmosphere exterior to
refrigerated or conditioned space; ambient, surrounding air.
Outside
Wall- Any wall that directly faces the outdoors.
Power
venting system – A
portion of a venting system using a fan or other mechanical means
to cause the removal of flue or vent gases under positive vent pressure.
R-value
– Thermal resistance value of an insulator.
Higher R-values mean better insulation and lower heat flow. R-values
are expressed in ft_. U/Btuh.
Radiation
gain – Heating increases due to the radiation
effects from the sun. Surfaces transfer heat.
Radiant
heat: Heat that passes through the air, heating
solid objects that in turn heat the surrounding area.
Refrigerant
Compressor – A specific machine, with or without
accessories, for compressing a given refrigerant vapor.
Relative
humidity – Approximately, the ratio of the
density of the water vapor in the air to the saturation density
of water vapor at the same temperature swing and equipment rating
conditions
Return
Air – Air removed from an approved conditioned
space or location and re circulated through the heating or cooling
appliance.
Room
Heater – A freestanding heating appliance
installed in the space being heated and not connected to ducts.
Seasonal
Energy efficiency ratio (SEER) – The total
cooling output of an air conditioner during its normal annual usage
period for cooling, in Btuh divided by the total electric energy
input during the some period, in watt-hours.
Sensible
gain – The increase in temperature where moisture
is not involved.
Solar
gain – Heat gain into a building form the
solar radiation through glass of different types and interior shading.
Also called “radiation gain”.
Static
pressure – The force per unit area, perpendicular
to the direction of flow in a duct.
Story
Above Grade – Any story having its finished
floor surface entirely above grade, except that a basement shall
be considered as a story above grade where the finished surface
of the floor above the basement is:
1. More than 6 feet above grade plan.
2. More than 6 feet above the finished ground level for more than
50% of the total building perimeter.
3. More than 12 feet above the finished ground level at any point.
Supply
Air – Air delivered to a conditioned space
through ducts or plenums from the heat exchanger of a heating, cooling
or ventilating system.
Temperature
difference – The variation between the inside
and outside air temperature. For cooling temperature difference,
solar gain data is considered.
Thermal
Resistance, R-Value – The inverse of the time
rate of heat flow through a body from one of its bounding surfaces
to the other for a unit temperature difference between the two surfaces,
under steady state conditions, per unit area.
Thermal
Transmittance, U-Factor – The coefficient
of heat transmission through a building envelope component or assembly,
equal to the time rate of rate flow per unit. Temperature difference
between the warm side and cold side air films.
Ton
– A time-rate of cooling equal to 12,000Btuh
(approximately 3517 W).
Total
latent load – The sum of the following latent
loads: internal gains, ventilation, and infiltration.
Total
sensible gain – The total of all sensible
gains for a room, including internal gains. Infiltration and duct
gains.
Transmission
loss – Heating or cooling loss through a solid
surface, such as a wall. (This differs from infiltration loss, which
is the heating or cooling loss through the air).
U-value
(or U Factor) – Combines the effect of the
thermal resistance of the wall, ceiling/roof, or glass, and the
effects of convection at the same inside and outside surfaces. U
values are expressed in Btuh/sq ft F
Unconditioned
Area – An area, which is protected from the
outdoor elements by the building envelope but has no mechanical
means of heating or cooling.
Unusually
Tight Construction – Construction in which:
1. Walls and ceilings comprising the building thermal envelope have
a continuous water vapor retard er with a rating of 1 perm or less
with openings therein gasket ed or sealed.
2. Storm windows or weather-stripping is applied around the threshold
and jambs of opaque doors and open able windows.
3. Caulking or sealants are applied to areas such as joints around
window and doorframes between sole plates and floors, between wall-ceiling
joints, between wall panels, at penetrations for plumbing, electrical
and gas lines, and at other openings.
Ventilation
– The natural or mechanical process of supplying
conditioned or unconditioned air to or removing such air from, any
space.
Venting
– Removal of combustion products to the outdoors.
Venting
System – A continuous open passageway from
the flue collar of an appliance to the outside atmosphere for the
purpose of removing flue or vent gases. A venting system is usually
composed of a vent or a chimney and vent connector, if used, assembled
to form the open passageway.
Wet-bulb
temperature – The temperature indicated by
a wet-bulb psychrometer. It is a good indicator of the amount of
moisture on the air. When the wet-bulb temperature is equal to the
dry-bulb temperature, the relative humidity is 100%.
Zone
– An area in a building that is isolated by
a full partition. A building can have several zones. You can adjust
the temperature in one zone independently of the other zones. The
number of zones in a house is equal to the number of thermostats
in the house. |